Dr. Andrei CECLAN, Prof. Dr. Eng. Vasile TOPA , Assoc. Prof. Dr. Eng. Dan Doru MICU, PhD. Stud. Levente CZUMBIL
Rezumat
Orice structura metalica, in special cele inalte de telecomunicatii, turnuri eoliene sau alt tip de turnuri metalice
pot servi ca si canale de descarcare pentru curenti de trasnet de ordinul sutelor de kA si astfel sa conduca la aparitia unor
potentiale electrice periculoase la nivelul solului. In aceasta lucrare sunt descrise si evaluate caracteristicile principale ale
campurilor electrice si magnetice generate in stratul superior al solului de diferite tipuri de curenti de trasnet care lovesc
turnuri metalice. Problema a fost abordata utilizand o platforma de simulari numerice, pentru diferite scenarii - curenti de
trasnet cu parametri diferiti, geometrii diferite de turnuri, rezistivitati diferite de sol, existenta sau nu a prizelor de
impamantare - evaluandu-se tensiunea de pas si campul magnetic in zona din apropierea turnului lovit.
Cuvinte cheie: curent de intoarcere a trasnetuluitensiune de pasturn metalic.
Abstract
Any metallic structure, especially tall ones like telecommunication, wind or other types of metallic towers can
become a discharging channel for lightning currents (hundreds of kA) and therefore give rise to potential dangerous events
on ground level. In this paper there are described and evaluated the main characteristics of the electric and magnetic fields
produced in the upper soil layer by different types of lightning currents flowing through a tall metallic structure, a tower
directly hit by lightning. The problem was addressed using the simulation environment of a software package. Simulations
were performed for several scenarios, in order to reflect the influence of analyzed parameters (lightning current shape,
tower geometry, soil resistivity and grounding system) over the ground potential rise, step voltages and magnetic fields in
the area nearby the stroked tower.
Keywords: lightning return stroke currentstep voltageground potential risemetallic tower
Din același număr
- AN ARTIFICIAL NEURAL NETWORK METHOD TO FORECAST ELECTRIC LOAD
- OPCOM’S ROLE IN THE WHOLESALE ELECTRICITY MARKET
- TIME FRAME MEASUREMENTS IMPACT ON PROBABILISTIC BEHAVIOUR OF PHOTOVOLTAIC SYSTEMS
- VIRTUAL INSTRUMENT FOR CALCULATION OF UNBALANCE FACTORS THROUGHS FORMULAS GIVEN IN INTERNATIONAL STANDARDS AND REGULATIONS
- AN ACTIVE MEASURING IMPEDANCE FOR SENSITIVITY IMPROVEMENT AT PARTIAL DISCHARGE MEASUREMENT IN POWER CABLES
- PI CURRENT CONTROLLER FOR GRID CONNECTED VSI IN DPGS APPLICATIONS
- CHARACTERISTICS OF VOLTAGE MAINTAINING METHODS FOR ELECTRICAL NETWORKS
- VIBRATION MONITORING SYSTEM OF A WIND TURBINE
- MINIMIZING THE FIR FILTER AREA USED IN A FPGA POWER COMPUTING INSTRUMENT
- DIGITAL EQUIPMENT FOR MONITORING THE CONDITION OF THE BUSHING RELATED TO THE HIGH POWER TRANSFORMER UNITS
- MODULAR SYSTEM FOR ACQUISITION, MONITORING AND PROCESSING ELECTRICAL PARAMETERS OF A DISTRIBUTION NETWORK
- THEORETICAL CHARACTERIZATION OF AN ELECTROMAGNETIC GENERATOR FOR VIBRATION ENERGY HARVESTING